thermal: fair_share: generalize the weight concept
The fair share governor has the concept of weights, which is the influence of each cooling device in a thermal zone. The current implementation forces the weights of all cooling devices in a thermal zone to add up to a 100. This complicates setups, as you need to know in advance how many cooling devices you are going to have. If you bind a new cooling device, you have to modify all the other cooling devices weights, which is error prone. Furthermore, you can't specify a "default" weight for platforms since that default value depends on the number of cooling devices in the platform. This patch generalizes the concept of weight by allowing any number to be a "weight". Weights are now relative to each other. Platforms that don't specify weights get the same default value for all their cooling devices, so all their cdevs are considered to be equally influential. It's important to note that previous users of the weights don't need to alter the code: percentages continue to work as they used to. This patch just removes the constraint of all the weights in a thermal zone having to add up to a 100. If they do, you get the same behavior as before. If they don't, fair share now works for that platform. Cc: Zhang Rui <rui.zhang@intel.com> Cc: Eduardo Valentin <edubezval@gmail.com> Cc: Durgadoss R <durgadoss.r@intel.com> Acked-by: Durgadoss R <durgadoss.r@intel.com> Signed-off-by: Javi Merino <javi.merino@arm.com> Signed-off-by: Eduardo Valentin <edubezval@gmail.com> (cherry picked from commit 5ef68023a611f0ff4f445758aef4f6a7ae3869fd) Signed-off-by: Jon Medhurst <tixy@linaro.org>
-rw-r--r--Documentation/thermal/sysfs-api.txt12
-rw-r--r--drivers/thermal/fair_share.c26
-rw-r--r--include/linux/thermal.h9
3 files changed, 36 insertions, 11 deletions
diff --git a/Documentation/thermal/sysfs-api.txt b/Documentation/thermal/sysfs-api.txt
index 5a8f0c09b208..afaf6057ad67 100644
--- a/Documentation/thermal/sysfs-api.txt
+++ b/Documentation/thermal/sysfs-api.txt
@@ -129,9 +129,15 @@ temperature) and throttle appropriate devices.
This structure defines the following parameters that are used to bind
a zone with a cooling device for a particular trip point.
.cdev: The cooling device pointer
- .weight: The 'influence' of a particular cooling device on this zone.
- This is on a percentage scale. The sum of all these weights
- (for a particular zone) cannot exceed 100.
+ .weight: The 'influence' of a particular cooling device on this
+ zone. This is relative to the rest of the cooling
+ devices. For example, if all cooling devices have a
+ weight of 1, then they all contribute the same. You can
+ use percentages if you want, but it's not mandatory. A
+ weight of 0 means that this cooling device doesn't
+ contribute to the cooling of this zone unless all cooling
+ devices have a weight of 0. If all weights are 0, then
+ they all contribute the same.
.trip_mask:This is a bit mask that gives the binding relation between
this thermal zone and cdev, for a particular trip point.
If nth bit is set, then the cdev and thermal zone are bound
diff --git a/drivers/thermal/fair_share.c b/drivers/thermal/fair_share.c
index 9e392d34ac9f..8c50b8d6afb7 100644
--- a/drivers/thermal/fair_share.c
+++ b/drivers/thermal/fair_share.c
@@ -59,13 +59,13 @@ static int get_trip_level(struct thermal_zone_device *tz)
}
static long get_target_state(struct thermal_zone_device *tz,
- struct thermal_cooling_device *cdev, int weight, int level)
+ struct thermal_cooling_device *cdev, int percentage, int level)
{
unsigned long max_state;
cdev->ops->get_max_state(cdev, &max_state);
- return (long)(weight * level * max_state) / (100 * tz->trips);
+ return (long)(percentage * level * max_state) / (100 * tz->trips);
}
/**
@@ -77,7 +77,7 @@ static long get_target_state(struct thermal_zone_device *tz,
*
* Parameters used for Throttling:
* P1. max_state: Maximum throttle state exposed by the cooling device.
- * P2. weight[i]/100:
+ * P2. percentage[i]/100:
* How 'effective' the 'i'th device is, in cooling the given zone.
* P3. cur_trip_level/max_no_of_trips:
* This describes the extent to which the devices should be throttled.
@@ -89,16 +89,32 @@ static long get_target_state(struct thermal_zone_device *tz,
static int fair_share_throttle(struct thermal_zone_device *tz, int trip)
{
struct thermal_instance *instance;
+ int total_weight = 0;
+ int total_instance = 0;
int cur_trip_level = get_trip_level(tz);
list_for_each_entry(instance, &tz->thermal_instances, tz_node) {
+ if (instance->trip != trip)
+ continue;
+
+ total_weight += instance->weight;
+ total_instance++;
+ }
+
+ list_for_each_entry(instance, &tz->thermal_instances, tz_node) {
+ int percentage;
struct thermal_cooling_device *cdev = instance->cdev;
if (instance->trip != trip)
continue;
- instance->target = get_target_state(tz, cdev,
- instance->weight, cur_trip_level);
+ if (!total_weight)
+ percentage = 100 / total_instance;
+ else
+ percentage = (instance->weight * 100) / total_weight;
+
+ instance->target = get_target_state(tz, cdev, percentage,
+ cur_trip_level);
instance->cdev->updated = false;
thermal_cdev_update(cdev);
diff --git a/include/linux/thermal.h b/include/linux/thermal.h
index 27a408ea9f35..14bcdeb9f0e0 100644
--- a/include/linux/thermal.h
+++ b/include/linux/thermal.h
@@ -242,9 +242,12 @@ struct thermal_bind_params {
/*
* This is a measure of 'how effectively these devices can
- * cool 'this' thermal zone. The shall be determined by platform
- * characterization. This is on a 'percentage' scale.
- * See Documentation/thermal/sysfs-api.txt for more information.
+ * cool 'this' thermal zone. It shall be determined by
+ * platform characterization. This value is relative to the
+ * rest of the weights so a cooling device whose weight is
+ * double that of another cooling device is twice as
+ * effective. See Documentation/thermal/sysfs-api.txt for more
+ * information.
*/
int weight;